VFD Input Phase Loss

VFD-PL1

Drive detected loss of one or more input power phases. Single-phasing causes DC bus ripple and potential damage.

high vfd
vfd phase loss single phase power fuse

Probable Causes (ranked)

Fix Steps

  1. 1 Measure all 3 input voltages at drive terminals — all should be within 3%
  2. 2 Check and tighten all input terminal connections
  3. 3 Test all input fuses with a meter — not visual, blown fuses can look intact
  4. 4 Inspect contactor contacts — look for pitting, measure contact resistance
  5. 5 If breaker suspected, load-test each pole or replace breaker
  6. 6 Check upstream connections at MCC or panel board

Field Trick

Clamp each phase at the drive input with a current meter. The missing phase will read zero or near-zero amps.

Suggested Replacement Parts

Parts matched to fault category: Fuse

Bussmann FRN-R-30 Time-Delay Fuse P/N: FRN-R-30 30A, 250V, Class RK5, dual element time-delay
Bussmann FRN-R-15 Time-Delay Fuse P/N: FRN-R-15 15A, 250V, Class RK5, motor circuit protection