VFD Overcurrent — Steady State

VFD-OC3

Drive tripped on overcurrent while running at constant speed. Current exceeded trip threshold during normal operation, not during accel or decel.

high vfd conveyor packaging palletizer
vfd overcurrent steady-state motor winding

Probable Causes (ranked)

Fix Steps

  1. 1 Monitor output current on VFD display during operation — compare to motor FLA
  2. 2 Check motor temperature with IR thermometer — compare all three phases at motor junction box
  3. 3 Megger VFD output cable from drive terminals to motor — disconnect both ends first
  4. 4 Check enclosure ambient temperature — install ventilation fan if above 40C
  5. 5 Compare all three output phase currents with clamp meter — more than 5% imbalance indicates motor or cable issue
  6. 6 If current is normal but fault persists, VFD current sensing board or CT may be faulty

Field Trick

Clamp all three motor leads through a single CT window — if the reading is not zero, you have a ground fault. On a healthy motor with balanced phases, the vector sum of all three phases is zero.

Suggested Replacement Parts

Parts matched to fault category: Vfd

Allen-Bradley PowerFlex 525 AC Drive 1HP P/N: 25B-D2P3N114 1HP, 480V, 3-phase, built-in EtherNet/IP, EMC filter
ABB ACS580 General Purpose Drive 2HP P/N: ACS580-01-05A7-4 2HP, 480V, built-in safe torque off, adaptive programming
GS20 AC Drive 1HP (Budget Option) P/N: GS20-20P5 1HP, 230V, sensorless vector, compact size — good replacement for testing

Prices are estimates. Verify part numbers match your equipment before ordering.

Need a deeper diagnosis with photo analysis and AI-powered troubleshooting?

Run Full Diagnosis
All Fault Codes