VFD Overcurrent Trip

VFD-OC1

Drive tripped on instantaneous overcurrent. Output current exceeded the hardware limit, shutting down to protect IGBTs.

high vfd conveyor packaging palletizer
vfd overcurrent igbt motor trip

Probable Causes (ranked)

Fix Steps

  1. 1 Disconnect motor cables at drive output terminals — if fault clears on start, problem is external
  2. 2 Megger motor cables: phase-to-phase and phase-to-ground, must be >1 MΩ
  3. 3 Check motor windings with LCR meter — phase balance within 5%
  4. 4 Verify drive parameter: motor rated current matches nameplate FLA
  5. 5 Inspect for mechanical binding — try to turn motor shaft by hand
  6. 6 Check acceleration time — too fast ramp causes current spike
  7. 7 If cable run >100ft, add output line reactor (3-5% impedance)
  8. 8 Replace drive if IGBT test fails (many drives have self-test in diagnostics menu)

Field Trick

Disconnect motor leads at the drive. If it still faults on start with nothing connected, the drive IGBTs are shot.