VFD Ground Fault

VFD-GF1

Drive detected current flow to ground on output side. Motor cable or motor insulation has broken down.

critical vfd conveyor packaging
vfd ground fault insulation megger motor

Probable Causes (ranked)

Fix Steps

  1. 1 Disconnect motor cables at drive — megger test phase to ground (>1 MΩ good)
  2. 2 If cable passes, disconnect at motor and test motor alone — megger at motor terminals
  3. 3 Inspect motor junction box for moisture, corroded connections, or wire damage
  4. 4 Check cable routing in conduit — look for pinch points, sharp edges, tight bends
  5. 5 If output reactor installed, disconnect and test separately
  6. 6 Dry out motor if moisture suspected — use space heater or low-voltage energize

Field Trick

Megger test at the drive first. If it fails, go to the motor end and test cable alone vs motor alone. The bad one will be obvious.