VFD Communication Loss

VFD-CL1

Drive lost communication with PLC or network controller. Commands cannot be sent or received over the fieldbus.

high vfd conveyor packaging
vfd communication ethernet modbus network plc

Probable Causes (ranked)

Fix Steps

  1. 1 Check network cable connections at drive and PLC/switch — reseat both ends
  2. 2 Verify communication module is fully seated and locked in drive
  3. 3 Check network LED indicators — link/activity lights should be solid/blinking
  4. 4 Verify drive node address is unique — check against network device list
  5. 5 Confirm baud rate/speed setting matches network configuration
  6. 6 For Modbus/serial: check wiring polarity (A/B), termination on last device
  7. 7 For EtherNet/IP: verify IP address, subnet, gateway settings

Field Trick

Swap to local control mode on the drive keypad. If motor runs fine in local, the problem is 100% communication — not the drive or motor.