VFD Current Fault During Accel

VFD-CF1

Drive faulted on overcurrent during acceleration ramp. Motor drawing excessive current trying to accelerate the load.

medium vfd conveyor packaging
vfd current acceleration ramp inertia

Probable Causes (ranked)

Fix Steps

  1. 1 Increase acceleration time — double current value and test
  2. 2 Check motor FLA vs drive rated current — drive must be >= motor FLA
  3. 3 Verify no mechanical binding during startup — try starting unloaded
  4. 4 Enable torque limit during acceleration if drive supports it
  5. 5 Check motor boost voltage parameter — reduce if motor saturating

Field Trick

Double the accel time. If it stops faulting, split the difference to find the minimum safe ramp time.