Piler Load Presence Sensor Fault

PIL-002

Load presence sensor on piler forks or platform not confirming product presence when expected, or showing false presence.

medium piler
piler load presence sensor photoeye alignment

Probable Causes (ranked)

Fix Steps

  1. 1 Clean sensor lens with dry cloth
  2. 2 Verify product is positioned within sensor detection zone
  3. 3 Realign sensor — use indicator LED on sensor body for feedback
  4. 4 Check wiring connections at sensor and PLC input
  5. 5 Adjust sensor sensitivity for the specific product being handled
  6. 6 Replace sensor if cleaning and alignment don't resolve

Field Trick

Block the sensor by hand. If the PLC input responds, the sensor works — product just isn't in the right spot. If PLC doesn't respond, check wiring.