Machine Won't Run — No Fault Code Showing

GEN001

Machine is in stopped state with no active fault on HMI. All fault indicators are clear but machine will not start from HMI start button.

medium general conveyor piler asrs packaging palletizer
start permissive mode selector estop ready interlock no fault

Probable Causes (ranked)

Fix Steps

  1. 1 Walk the entire machine — check every E-stop, twist/pull each one, check all guard doors
  2. 2 Check mode selector switch on main control panel — verify it is in AUTO/RUN position
  3. 3 Look at HMI for any permissive status screen — identify which ready condition is not met
  4. 4 Verify upstream equipment (conveyors feeding this machine) is running and in auto mode
  5. 5 Verify downstream equipment is running and not full or faulted
  6. 6 Check main air pressure gauge — must be above minimum (typically 80 PSI)
  7. 7 Check VFD and servo drive displays for any fault codes or non-ready indicators
  8. 8 Try pressing HMI Reset or Alarm Silence first, wait 5 seconds, then press Start
  9. 9 If machine was mid-cycle when stopped, try pressing Cycle Reset before Start

Field Trick

On most PLCs, the Start button input and the machine Running output are in different rungs. If pressing Start does nothing, use the PLC status screen to check if the Start input is being received. If yes, the problem is in the permissive logic. If no, the problem is in the HMI or start button wiring.

Suggested Replacement Parts

Parts matched to fault category: Safety Relay

Allen-Bradley Guardmaster 440R-N23126 P/N: 440R-N23126 Dual-channel safety relay, 24VDC, 3 N.O. + 1 N.C., Cat 4 / PLe
Pilz PNOZ X3 Safety Relay P/N: 774310 24VDC/AC, 3 N.O. + 1 N.C., E-stop and safety gate monitoring

Prices are estimates. Verify part numbers match your equipment before ordering.