AS/RS Fire Detection / Suppression Activation

ASRS-FIRE1

Fire detection system in the AS/RS rack structure has activated. Crane operations are halted. Fire suppression may have been deployed.

critical asrs
asrs fire detection suppression sprinkler safety alarm

Probable Causes (ranked)

Fix Steps

  1. 1 FIRST: Confirm if there is an actual fire — do NOT assume it is a false alarm
  2. 2 If fire confirmed, follow facility emergency action plan — evacuate, call fire department
  3. 3 If confirmed false alarm, identify which detector zone activated — check fire alarm panel annunciator
  4. 4 Check the triggered detector — replace if contaminated, end-of-life, or physically damaged
  5. 5 If sprinkler head activated, water damage to stored product is likely — begin assessment immediately
  6. 6 Fire system reset must be performed by qualified fire alarm technician
  7. 7 Crane restart requires fire system all-clear AND manual verification of AS/RS structure integrity

Field Trick

After a sprinkler activation in an AS/RS, check the rack structure for water damage to cardboard loads BEFORE running the crane. Water-soaked pallets of cardboard weigh 3x their normal weight and can exceed rack capacity. A collapsed rack section from overweight wet pallets is a catastrophic secondary event.