Allen-Bradley PanelView HMI Communication Fault

AB-PV-HMI

PanelView or PanelView Plus HMI lost communication with the ControlLogix/CompactLogix PLC. Screen displays communication error or tag values show as '####' or 'Comm Err'.

high allen-bradley conveyor packaging palletizer piler asrs
allen-bradley panelview hmi communication factorytalk rslinx display

Probable Causes (ranked)

Fix Steps

  1. 1 Check Ethernet cable at HMI and switch — verify link LED on both ends
  2. 2 Verify PLC is in RUN mode — check keyswitch or RSLogix 5000
  3. 3 Ping PLC IP address from HMI terminal settings or from a laptop on the same network
  4. 4 In FactoryTalk View ME/SE, check RSLinx Enterprise shortcut paths — controller name must match PLC
  5. 5 Restart the HMI application — press Ctrl+Alt+Del on PanelView Plus to access Windows desktop if needed
  6. 6 If multiple HMIs on the network, check for IP conflicts — each must have a unique IP
  7. 7 Power cycle the HMI as last resort — hold power button or cycle the 24VDC supply