Allen-Bradley PLC Major Fault — Power Loss (Type 01)

AB-PLC-MAJOR01

CompactLogix or ControlLogix processor detected a power-up or power-cycle event. Controller faulted on startup or after a brown-out condition. Program execution stopped.

critical allen-bradley conveyor packaging palletizer piler asrs
allen-bradley plc controllogix compactlogix major fault power loss 1756 1769

Probable Causes (ranked)

Fix Steps

  1. 1 Check PLC power supply output voltage — 1756-PA72 should read 5.1V and 24V on status LEDs
  2. 2 Measure incoming AC voltage at power supply terminals — should be stable 120VAC or 240VAC
  3. 3 Reseat the CPU module firmly into the backplane — push until retention clips click
  4. 4 Check power budget — sum all module current draw and compare to power supply rating in RSLogix
  5. 5 If power loss is intermittent, add a 24VDC UPS to the panel or check utility power quality
  6. 6 Clear the major fault in RSLogix 5000/Studio 5000 — Controller Properties > Major Faults tab
  7. 7 After clearing, put controller back in RUN mode — verify program executes normally

Field Trick

In RSLogix 5000, go to Controller Properties > General > Major Faults. The timestamp tells you exactly when the power event occurred. Cross-reference with building power logs to confirm utility vs internal cause.