PowerFlex 525 STO safety input is de-energized. Drive output is hardware-disabled by the built-in STO function. This is a designed safety feature, not a drive malfunction.
New PowerFlex 525 drives out of the box will NOT run until you either connect the STO inputs to 24VDC or install the jumper wires. This catches a lot of people during commissioning. Check terminals 01 and 02 — they need 24VDC from a safety-rated source or jumpered.
Parts matched to fault category: Safety Relay