PowerFlex 525 Fault F002 — Auxiliary Input

AB-PF525-F2

PowerFlex 525 external fault input is active. Digital input configured as 'Auxiliary Fault' is seeing an active signal from an external device (thermistor, pressure switch, flow switch, etc.).

medium allen-bradley vfd
allen-bradley powerflex 525 auxiliary digital input external fault

Probable Causes (ranked)

Fix Steps

  1. 1 Identify which digital input is configured as Aux Fault — check P033 [Digital In1 Sel] through P038
  2. 2 Trace wiring from that digital input terminal back to the external device
  3. 3 Check external device status — is the thermal switch tripped, pressure switch open, etc.
  4. 4 Measure voltage at the digital input terminal — 24VDC present or absent tells you the circuit state
  5. 5 If external device is healthy, check wiring continuity end-to-end
  6. 6 If you need to bypass temporarily for troubleshooting, change the digital input function to 'Not Used' — but restore before production

Field Trick

On a PowerFlex 525, the Aux Fault input is often wired to a motor thermistor relay. If the motor is cool and the fault is active, check the thermistor relay itself — the relay contact may have failed. Bypass the relay temporarily (not the thermistor) to confirm.

Suggested Replacement Parts

Parts matched to fault category: Vfd

Allen-Bradley PowerFlex 525 AC Drive 1HP P/N: 25B-D2P3N114 1HP, 480V, 3-phase, built-in EtherNet/IP, EMC filter
ABB ACS580 General Purpose Drive 2HP P/N: ACS580-01-05A7-4 2HP, 480V, built-in safe torque off, adaptive programming
GS20 AC Drive 1HP (Budget Option) P/N: GS20-20P5 1HP, 230V, sensorless vector, compact size — good replacement for testing

Prices are estimates. Verify part numbers match your equipment before ordering.

Need a deeper diagnosis with photo analysis and AI-powered troubleshooting?

Run Full Diagnosis
All Fault Codes