PowerFlex VFD Fault F002 — Auxiliary Input

AB-PF-F002

PowerFlex 525/527 drive faulted on auxiliary input (digital input configured as fault input). External device signaled a fault condition to the drive.

high allen-bradley conveyor packaging palletizer piler
allen-bradley powerflex vfd drive F002 auxiliary input 525 527

Probable Causes (ranked)

Fix Steps

  1. 1 Identify what device is wired to the drive's digital input configured as Aux Fault — check panel drawings
  2. 2 Check the external device status — reset if tripped, verify normal condition
  3. 3 If motor thermistor, check motor temperature — let cool before resetting drive
  4. 4 Verify wiring from external device to drive terminal — check for broken wire or loose terminal
  5. 5 Reset drive fault from keypad, digital input, or via network command
  6. 6 In drive parameters, check which digital input is configured for 'Auxiliary Fault' (Parameter group A06x)

Field Trick

Parameter A06x in the PowerFlex 525 shows which digital input is configured as the fault input and whether it is normally open or normally closed. Check this first — the aux input might be inverted from what you expect.

Suggested Replacement Parts

Parts matched to fault category: Vfd Drive

Allen-Bradley PowerFlex 525 AC Drive 1HP P/N: 25B-D2P3N114 1HP, 480V, 3-phase, built-in EtherNet/IP, EMC filter
ABB ACS580 General Purpose Drive 2HP P/N: ACS580-01-05A7-4 2HP, 480V, built-in safe torque off, adaptive programming
GS20 AC Drive 1HP (Budget Option) P/N: GS20-20P5 1HP, 230V, sensorless vector, compact size — good replacement for testing

Prices are estimates. Verify part numbers match your equipment before ordering.

Need a deeper diagnosis with photo analysis and AI-powered troubleshooting?

Run Full Diagnosis
All Fault Codes