GuardLogix safety controller reports safety signature does not match expected value. Safety program may have been modified without validation.

critical allen-bradley
allen-bradley guardlogix safety signature validation

Probable Causes (ranked)

Fix Steps

  1. 1 Compare current safety signature to documented approved signature
  2. 2 If program was intentionally modified, complete safety validation per site procedure
  3. 3 If unintentional, reload the approved safety program version from backup
  4. 4 Record new safety signature in safety documentation after validation
  5. 5 Lock safety task after validation to prevent unauthorized changes

Field Trick

Safety signature must match what's on the validation document. If it doesn't match, someone changed the safety program. Lock it down and investigate.