RepairXpert Industrial Automation

PowerFlex Fault Code F33 - Auto Rstrt Tries

AB-F006

PowerFlex drive exhausted all automatic restart attempts. Drive faulted repeatedly and gave up trying to restart.

high allen-bradley vfd
allen-bradley powerflex auto restart recurring fault

Probable Causes (ranked)

Fix Steps

  1. 1 Check fault log/queue on drive — the fault BEFORE F33 is the real problem
  2. 2 Fix the underlying recurring fault (usually OC, OV, UV, or GF)
  3. 3 Check motor and cables for intermittent problems
  4. 4 Review auto restart settings: number of tries, delay between tries
  5. 5 If power quality issue, add line reactor or investigate facility power
  6. 6 Manual reset required after F33 — clearing the root cause is mandatory

Field Trick

F33 is never the real fault. Scroll back in the fault log — the fault right before it is what you need to fix.

Suggested Replacement Parts

Parts matched to fault category: Vfd Drive

Allen-Bradley PowerFlex 525 AC Drive 1HP P/N: 25B-D2P3N114 1HP, 480V, 3-phase, built-in EtherNet/IP, EMC filter
ABB ACS580 General Purpose Drive 2HP P/N: ACS580-01-05A7-4 2HP, 480V, built-in safe torque off, adaptive programming
GS20 AC Drive 1HP (Budget Option) P/N: GS20-20P5 1HP, 230V, sensorless vector, compact size — good replacement for testing

Prices are estimates. Verify part numbers match your equipment before ordering.

Need a deeper diagnosis with photo analysis and AI-powered troubleshooting?

Run Full Diagnosis
All Fault Codes