EtherNet/IP Connection Timeout

AB-F003

PLC lost EtherNet/IP connection to a remote device. Communication timed out waiting for response.

high allen-bradley
allen-bradley ethernet communication timeout network

Probable Causes (ranked)

Fix Steps

  1. 1 Check physical cable at both ends — look for link LED on switch port
  2. 2 Ping remote device IP from a laptop on the same subnet
  3. 3 Check remote device for power and local faults
  4. 4 Verify no IP address conflicts — scan network with Wireshark or RSLinx
  5. 5 Increase RPI from 10ms to 20ms or 50ms to reduce network load
  6. 6 If using unmanaged switch, verify port speed autonegotiation
  7. 7 Check for IGMP snooping on managed switches to reduce multicast traffic

Field Trick

Bring a laptop with RSLinx. If you can browse to the device but the PLC can't, it's an RPI/connection timeout setting, not a cable problem.