ControlLogix Firmware Flash Required After Replacement

AB-CLGX-FW

A replacement 1756 module has been installed but its firmware version does not match the project configuration. Module is faulted or inhibited until firmware is updated.

medium allen-bradley plc
allen-bradley controllogix 1756 firmware controlflash replacement upgrade

Probable Causes (ranked)

Fix Steps

  1. 1 In Studio 5000, right-click the module > Module Properties > General tab to see required vs. actual firmware revision
  2. 2 Open Rockwell ControlFLASH utility on the engineering PC
  3. 3 Browse to the module through the USB or Ethernet path
  4. 4 Select the target firmware version that matches the project requirement
  5. 5 Flash the module — do NOT interrupt the process (takes 2-10 minutes depending on module)
  6. 6 After flash completes, power cycle the chassis if prompted
  7. 7 Re-download the program if the controller cleared its memory during the process

Field Trick

Keep a USB drive with the ControlFLASH firmware files for every module type in your chassis. Download the firmware kit from Rockwell's website once per year. When you need to flash a module at 2 AM, you don't want to be downloading firmware files on a plant floor laptop with spotty WiFi.