PLC Communication Fault — Serial Link Down

60002

Serial communication link (RS-232/RS-485) between PLC and device has failed. Data exchange stopped.

high general conveyor piler asrs packaging palletizer
plc communication serial rs485 rs232

Probable Causes (ranked)

Fix Steps

  1. 1 Reseat serial cable at both ends — inspect for bent or broken pins
  2. 2 Verify communication parameters match at both ends: baud rate, parity, stop bits, station address
  3. 3 Check RS-485 termination — 120 ohm resistor required at each physical end of the bus
  4. 4 Route serial cable away from power cables and VFD wiring — 6 inch minimum separation
  5. 5 Substitute serial cable with known-good cable to rule out cable failure
  6. 6 Test with serial monitor software on laptop to confirm data is being sent/received